Article image

Item no.: 7309200

Refix DT 100

expansion vessel, green, 10/4 bar

Technical data

Type

DT 100

Colour

green

Diaphragm material

butyl

Nominal volume

100 l

Max. useful volume

75 l

Max. permissible system temperature

70 °C

Min. perm. operating temperature

-10 °C

Max. perm. operating temperature

70 °C

Max. perm. operating pressure

10 bar

Factory provided gas supply pressure

4 bar

Number of connections

2 St.

Connection

Rp 1 1/4"

Diameter

480 mm

Height

834 mm

High water connection

56 mm

Tilt dimension approx.

895 mm

Weight

17.00 kg

EAN code

4036705001499

Product details

Refix DT
Flowed through diaphragm expansion tank for DHW systems, water supply installations and pressure-boosting systems. With diaphragm according to the elastomer directive and W 270. Exterior and interior coating in compliance with KTW-A. Only suitable for cold water systems. Up to Rp 1 1/4" including flowjet flow fitting, from DN50 including Duo flange connection piece with flow facility.

Built according to DIN EN 13831 and VDI 4708 or AD 2000. Approval according to Pressure Equipment Directive 2014/68/EC.

  • Flowjet incl. shut-off and draining or dual connection
  • replaceable bladder according to DIN EN 13831, DIN 4807 T5, KTW-C and W270, built and tested to DIN 4807 T5, DIN DVGW Reg. No. NW-0411AT2534
  • interior and exterior coating in compliance with KTW-A, durable epoxy resin coating
  • sleeve for optional membrane rupture detector
  • pressure gauge and supply pressure valve protected by clip
  • only for use in cold water pipes (consider installation and operating instructions)

Downloads

Accessories

optional
Article image

9119198 - Digital system pressure test device

Digital pressure gauge
Manual pressure gauge to check the gas pressure at the expansion vessel.

With illuminated display. Display range up to 9.0 bar.

optional
Article image

7857700 - diaphragm rupture detector MBM II

Membrane rupture detector
Electrode with evaluation relay for installation in an expansion vessel with an appropriate connection. Vessel must be pre-equipped for electrode (please note when ordering)

Inclusive of electrode relay for signal measurement for installation in installer-supplied control cabinet or for local installation.

  • power supply 230 V/50 Hz
  • floating output (changeover contact)

Contact the Reflex Team and further information

Reflex Solutions Pro

  • Free to use
  • Simple and self-explanatory
  • Detailed documentation
Reflex Solutions Pro

Reflex Solutions Pro allows you to design every Reflex and Sinus product into your project quickly and easily. After entering a few system parameters you will receive your custom product solution with all the relevant documentation.