Not a current portfolio product. Contents are for documentation purposes only.

Article image

Item no.: 8812100

Fillcontrol Plus 1,4

monitoring/makeup for systems with diaphragm expansion vessel

Technical data

Type

Plus 1,4

Max. perm. operating temperature

90 °C

Max. perm. operating pressure

10 bar

Inlet/outlet connection

G 3/4" / G 1/2"

Electric connection

230V/50Hz

Flow rate characteristic value kvs

1.4 m³/h

Flow rate characteristic value kvs with Fillset

0.7 m³/h

Height

292 mm

Width

340 mm

Depth

270 mm

Weight

5.60 kg

EAN code

4036705114762

Product details

Fillcontrol Plus
Function monitoring of the pressurisation in sealed heating and chilled water systems and controlled make-up of make-up water plus filling function for first filling and refilling.

Including controlled replenishment of make-up water when the system pressure is undershot, as well as proprietary operating mode for system first filling and refilling, with CE marking.

Functional unit comprising a hydraulic part and a Control Basic operating unit. Both are installed in an ergonomic and maintenance-friendly manner on a bracket for wall mounting.

The hydraulic scheme comprises shut-off valve, make-up solenoid valve and electronic pressure sensor.The Control Basic control unit is integrated in a robust plastic housing in which both the power and communication electronics and the control panel with dirt-resistant membrane-covered keyboard is housed.

Control Basic is a fully automatic, freely configurable microprocessor control with real-time clock, differentiating error and parameter memory, two line plain text display for system pressure and all relevant operating and fault messages, LED display for operating modes and general error messaging.

Communication electronics comprising:

  • RS 485 port as data interface or for the connection of optional communication components
  • Potential-free output for the forwarding of the collective message
  • Input for signal processing of a contact water meter
  • Input for function requesting via an external signal

Control unit completely wired ready for connection according to VDE regulations with mains power cable and mains plug.

System pressure monitoring and display with fault message upon undershooting of the minimum pressure or exceeding of the maximum pressure. Actuation takes place via an integrated system pressure interpretation unit or an external 230V signal (e.g. a pressurisation station) with automatic interruption and fault messaging upon exceeding of the running time and/or the number of cycles. Controlled make-up, automatic interruption and fault message upon exceeding of the runtime and/or the number of cycles.

Evaluation option provided by a contact water meter including optional possible capacity monitoring of ion exchangers in the make-up line.

Documentation and control of the entire system in respect of the above mentioned parameters.

Downloads

Accessories

optional
Article image

7945723 - Commissioning Fillcontrol Auto/Auto Compact/Smart

Service description:
commissioning of Fillcontrol Auto, Fillcontrol Auto Compact and Fillcontrol Smart by the customer service, comprising:
  • Adjustment of system to the operating parameters specified by the client,
  • Checking the settings and operating parameters, and the system's performance and function in the overall system,
  • All set values documented in a report.

Requirements:

  • The static expansion vessels of all make-up systems must be preset to the pressure specified in the installation and operating instructions.

Customer benefits:
While it is entirely possible for customers to put a recently purchased system into service themselves, there are a number of reasons why commissioning by Reflex is a better idea.

  • Certainty that the system is set up for optimum operation
  • Excluding of possible damage due to incorrect commissioning thus reliability and avoidance of time and costs for downtimes

Commissioning date:
the service can take place within the local country inside about three weeks, internationally within about six weeks after placing of the corresponding order.
Services provided by Service are net! The price does not include any site waiting times or work arising from improper installation or improper condition.